 ED 100 SG Primary protection

 Datasheet

 

This surge protector is designed to meet international standard IEC61643-11, type I test, and German standard VDE0675/6, Class B. The technology used is the "encapsulated air spark gap", which can handle very high lightning currents (35kA for one pole with 10/350µs impulse) and ensure spontaneous quenching on the short-circuit current of the AC network (up to 2kA rms). The ED100SG can be used to protect a single-phase network (2xED100SG in common mode) or a three-phase network (4 or 3xED100SG). The air tightness of the spark gap allows standard installation (no expulsion of gas in operation). For a maximum protection efficiency, especially in terms of protection level, the ED100SG should be used in combination with ED50 secondary surge protectors. 

Technical data
ED 100 SG
Nominal voltage UN 230V
Disconnection fuse 160A
Max. operating voltage UC 280V
Nominal discharge current 
(8/20 µs-15times) I
N
50kA
Maximum discharge current (8/20 µs) IMAX 100kA
Maximum lightning current (10/350 µs) IIMP >35kA
Protection level Up (at IIMP) <4kV
Admissible short-circuit current Icc 50kA
Follow current quench capacity 2kA