ED 150-275 Primary protection (improved version)

Datasheet

 

 

The ED150 surge protection is designed to protect, against direct and indirect effects of lightning, the low voltage network of an installation. The ED150 is particularly useful in the high keraunic level area where the risk of heavy surge current or even direct strike is high. The ED150 is able to protect a single phase (2 x ED150 in common mode) or a 3 phase (4 or 3 x ED150) network.

The ED150 is unique because of the very low residual voltage, 800V (at 15kA acc. to 10/350µs). This product is designed to withstand a 25 kA-10/350 µs Lightning impulse (similar to the effect of a direct strike on the building) : the "no-gap" technology used allows the better behaviour possible regarding the LV network (no follow current).

To meet the various national or international SPD standards, the ED150 includes a "2-level" thermal disconnection mechanism as well as fault indicators and a switch for remote signalisation.

It's also available in 120V, 320V and 400V versions.

The device is UL approved acc to UL1449.

 

Technical data
ED150...
Nominal voltage Un  230V
Max. continuous operating Voltage Uc  275V (version with 330V is also available)
Follow current If none
Nominal discharge current (8/20 µs-15ggr) IN 70kA
Max. discharge current IMAX (8/20 µs)  150kA
Max.lightning current (10/350 µs) IIMP 25kA
Continuous operating current IC (at UC) <2mA
Reaction time <25ns
Protection Level Up
(Residual Voltage UP at 15kA 10/350µs) 
<800V
Plastic material UL94-5VA
connection area 4-50mm2
Temperature area -40/+85oC