Till start

ED40














ED 50 secondary protection

Datasheet

   

ED50 surge protections are used mainly for the secondary protection of single- and three-phase networks on the main electrical switchboard.

They provide common-mode protection (between the active conductors and earth) and are available in single-phase and three-phase versions and in a "remote signalling" version (ED50S). The ED50-400 is especially well suited to IT network. 

Available in 120V, 230V, 320 and 400V versions.

Max lightning current (10/350µs) 5kA
Maximum discharge current Imax (8/20µs) 40kA
Protection level U <1,3kV at 20kA (8/20µs) for the 230V version
Connection area 4-50mm2
Service temperature -40oC till +80oC
Max. operating current Ic  <1mA