ED 250 Type I, II and III

The ED250 surge protection is designed to protect, against direct and indirect effects of lightning, the low voltage network of an installation. The ED250 is particularly useful in the high keraunic level area where the risk of heavy surge current or even direct strike is high. The ED250 is able to protect a 3 phase (both TNC and TNS) network.

The ED250 is unique because of the very low residual voltage, 900V (at 15kA acc. to 10/350µs). This product is designed to withstand a 25 kA-10/350 µs lightning impulse (similar to the effect of a direct strike on the building) : the "no-gap" technology used allows the better behaviour possible regarding the LV network (no follow current).

To meet the various national or international SPD standards, the ED250 includes a thermal disconnection mechanism as well as fault indicators and a switch for remote signalisation.

It's also available in 120V, 320V and 400V versions.

ED250 follows the standards: SS-EN 61643-11 (Swedish), IEC 61643-11 (International), UL 1449-ed2 (USA), NFC 61740-95 (France) and VDE 0675-6 (Germany).

Data sheet

Download PDF

Technical data

Nominal voltage Un 230V
Max. continuous operating Voltage Uc 275V (version with 330V is also available)
Follow current If none
Nominal discharge current (8/20 µs-15ggr) IN 40kA
Max. discharge current IMAX (8/20 µs) 80kA
Max.lightning current (10/350 µs) IIMP 25kA
Continuous operating current IC (at UC) <2mA
Max back-up fuse (If mains is >250A) 250A
Reaction time <25ns
Protection Level Up
(Residual Voltage UP at 15kA 10/350µs)
<900V
Plastic material UL94-5VA
connection area 2.5-50mm2
Temperature area -40/+85oC

 